Two control panel standards come up again and again in UK specifications: BS EN 61439 and BS EN 60204-1. They are not alternatives. BS EN 61439 is the product standard for low-voltage switchgear and controlgear assemblies, the panel as a piece of equipment in its own right. BS EN 60204-1 covers the electrical equipment of a machine, including the panel that controls it. Which one leads depends on what the panel is for, and many machine panels draw on both.

Control panel standards at a glance

Question BS EN 61439 BS EN 60204-1
What it covers Low-voltage switchgear and controlgear assemblies: the panel as a product The electrical equipment of a machine, including its control panel
Typical panels Distribution boards, motor control centres, stand-alone power panels Panels built for a particular machine or production line
Voltage range Up to 1,000 V a.c. or 1,500 V d.c. Up to 1,000 V a.c. or 1,500 V d.c.
Main focus Proving the design (temperature rise, short-circuit withstand, insulation) and checking every build Safe machine operation: isolation, emergency stop, control circuits, protective bonding, documentation
Who answers for it The original manufacturer (design) and the assembly manufacturer (build) The machine manufacturer, as part of the machine’s conformity

BS EN 61439: the panel as a product

BS EN 61439 is a series; newer British editions include IEC in the designation, for example BS EN IEC 61439-1:2021. Part 1 sets the general rules and is never used on its own; the other parts are product standards for particular kinds of assembly:

  • Part 2: power switchgear and controlgear assemblies, which covers most industrial power and motor control panels
  • Part 3: distribution boards intended to be operated by ordinary persons
  • Part 4: assemblies for construction sites
  • Part 5: assemblies for public power distribution networks
  • Part 6: busbar trunking systems

Design verification

The design must be verified against the applicable requirements, with the effect of any change assessed against that verified design. The standard lists the characteristics to verify, including strength of materials, degree of protection (IP), clearances and creepage distances, protection against electric shock, dielectric properties, temperature rise, short-circuit withstand strength, EMC and mechanical operation. The permitted methods depend on the characteristic: testing, comparison with a verified reference design, or assessment using the calculations and design rules allowed by the standard. These methods are not interchangeable for every requirement.

Routine verification

Every panel built is then checked before it goes into service: degree of protection, clearances and creepage distances, continuity of protective circuits, built-in components, internal wiring and connections, terminals, mechanical operation, dielectric properties and function. These checks are non-destructive, and they do not replace the installer’s own testing on site under BS 7671.

Who is responsible

The standard separates the original manufacturer, who designs the system and carries out design verification, from the assembly manufacturer, who builds the panel and carries out routine verification. A panel builder who departs from the original manufacturer’s tested arrangements takes on the original manufacturer’s responsibilities for those changes.

BS EN 60204-1: the panel as part of a machine

BS EN 60204-1 starts where the machine’s electrical equipment connects to the supply, and covers the electrical equipment of the whole machine. For a control panel, that brings in requirements such as:

  • the supply disconnecting device and isolation
  • protection against electric shock and protective bonding
  • overcurrent protection and determining the short-circuit rating
  • control circuits, emergency stop and safe torque off
  • EMC
  • marking, documentation and verification testing

It is the electrical standard machine builders most often use to show that a machine’s electrical equipment meets the machinery rules. BSI lists BS EN 60204-1:2018+A1:2025 as the current British edition. Specify the applicable edition and review the actual requirements and amendments; a short overview is not a substitute for the standard.

Where the two standards meet

BS EN 60204-1 addresses the machine’s electrical equipment as a whole. Relevant component and assembly product standards may also apply. For a motor control assembly within that equipment, assess the relevant BS EN 61439 requirements alongside BS EN 60204-1.

Do not choose between the standards solely by panel size or current rating. Define the assembly’s function, scope and interfaces, then agree the applicable requirements and verification with the responsible designer. Temperature rise and short-circuit performance need attention in any panel, including compact designs.

The legal background in Great Britain

A stand-alone panel may fall within the Electrical Equipment (Safety) Regulations 2016 where its rated voltage and product category are in scope: generally 50–1,000 V a.c. or 75–1,500 V d.c., subject to exclusions. A panel incorporated into machinery also needs to be considered within the machine’s conformity assessment. EMC requirements may apply too; classification depends on what is supplied and how it is used.

Standards are generally voluntary. A relevant designated or harmonised standard can support a presumption of conformity only for the legal requirements it covers, subject to the applicable listing and conformity route. Specify the editions and check the legislation for the destination market and supply date.

Choosing control panel standards for your project

  • A distribution board, motor control centre or stand-alone power panel: select the relevant BS EN 61439 product part for the assembly and intended users, with routine verification of every assembly. Part 2 and Part 3 have different scopes.
  • A control panel built for one machine or line: BS EN 60204-1 as part of the machine, with the relevant BS EN 61439 assembly requirements assessed where applicable.
  • A replacement or upgraded panel on an existing machine: BS EN 60204-1 for the machine’s electrical equipment, plus a check on whether the change affects the machine’s safety functions.

What to put in your panel specification

Many problems with panels start with what was never written down. A good specification states:

  • the standards the panel must meet, and which part of BS EN 61439 where it applies
  • the supply: voltage, frequency, earthing system and the prospective short-circuit current at the point of connection
  • the incoming protective device
  • the installation environment: IP rating, ambient temperature, humidity, pollution, altitude, washdown or outdoor use
  • current ratings, including expected diversity
  • the form of separation, if internal separation is needed
  • access, isolation and maintenance arrangements, and space for future expansion
  • the documentation you need: drawings, test certificates and routine verification records

How Advanced Automation can help

We design, build and test PLC and motor control panels to the relevant standards, including BS EN 61439 and BS EN 60204-1, so they arrive on site ready to install. Every panel is tested before it leaves, witnessed factory acceptance tests are available, and each one comes with full drawings and test records. We can work from your specification, or help you write one.

Find out more about our control panel service, or send us your panel requirements.

Frequently asked questions

What is the difference between BS EN 61439 and BS EN 60204-1?

BS EN 61439 is the product standard for low-voltage switchgear and controlgear assemblies. BS EN 60204-1 covers the electrical equipment of machines, including their control panels. Many machine panels draw on both.

Does BS EN 61439 apply to machine control panels?

BS EN 60204-1 addresses the machine’s electrical equipment. Relevant BS EN 61439 requirements may also apply to switchgear or controlgear assemblies within it. The decision depends on the assembly’s function and scope, not simply its size or current rating.

What is routine verification under BS EN 61439?

Non-destructive checks carried out on every panel before it goes into service, covering degree of protection, clearances, protective circuit continuity, wiring and connections, mechanical operation, dielectric properties and function.

What should a control panel specification include?

The standards to meet; the supply voltage, earthing system and prospective short-circuit current; the incoming protective device; the installation environment and IP rating; current ratings; and the documentation and test records you need.

Who is responsible for BS EN 61439 compliance?

The original manufacturer is responsible for design verification, and the assembly manufacturer (the panel builder) for routine verification of each panel. A builder who departs from the original design takes on design responsibility for those changes.

Sources and further reading

Sources checked 28 October 2026. Confirm current component availability, standards and legal requirements for your project.